Application and energy saving of plate heat exchanger in data center

1, water cooling system
From 2005 to 2009, the Internet industry developed rapidly, and the demand for data services soared. Data centers with small scale and low power density had to bear a lot of IT equipment. At this time, the power density of the single cabinet has increased to 3~5kw, and the size of the data center has gradually increased. Medium-sized data centers with hundreds to thousands of cabinets have begun to appear. As the scale has grown, data center energy consumption has increased dramatically, and energy conservation issues have begun to receive attention.
The traditional air-cooled direct expansion system has lower energy efficiency than COP (Coefficient Of Performance). The COP in Beijing is about 2.5~3.0. The air-conditioning equipment consumes a lot of power and accounts for a high proportion of the overall power consumption of the data center. Moreover, with the expansion of installed capacity, the installation position of the air-cooled condenser reserved in the original data center building is seriously insufficient, and the noise disturbance problem is prominent, which restricts the expansion of the data center. At this time, the chilled water system widely used in office buildings began to be gradually applied to the data center refrigeration system. Since the COP of the chiller can reach 3.0~6.0, the large centrifugal chiller is even higher, and the chilled water system can greatly reduce the data. The center operates energy consumption.
The chilled water system is mainly composed of a chiller, a cooling tower, a chilled water pump, a cooling water pump, and a chilled water type air conditioner end. The system adopts centralized cold source, the cooling efficiency of the chiller is high, and the cooling tower is placed in a flexible position, which can effectively control the noise and benefit the aesthetic appearance of the building. After reaching a certain scale, it has more construction cost and maintenance cost than the direct evaporative system. Economic advantage.
Cooling system
The end of the air-conditioning system used in the chilled water system is a chilled water-type precision air conditioner, and its single cooling capacity can reach more than 150kw. The air supply mode and the previous air-cooled direct expansion system have not changed much, only the cooling medium in the end changes. The air conditioning equipment is still far away from the IT heat source, and mainly relies on the air-conditioning fan to deliver air to maintain the airflow organization.
 2, plate heat exchanger and water cooling system natural cooling
From 2010 to the present, with the development of data center cooling technology and people's further attention and pursuit of data center energy consumption, the concept of natural cooling has gradually been applied to the data center.
In the northern part of China, the outdoor temperature is lower in winter, and the water side natural cooling system is used. In winter, there is no need to open the mechanical refrigeration unit, and the cooling tower and the plate heat exchanger are used to “free” to obtain the cold source, thereby reducing the energy consumption of the data center. The water side natural cooling system is a set of plate heat exchangers and related switching valve groups above the original chilled water system. The chiller mechanical cooling is still used in high temperature weather, and the low temperature cooling water prepared by the cooling tower is used in the low temperature season. The high-temperature chilled water is exchanged for heat. In the transitional season, the lower-temperature cooling water and the higher-temperature chilled water are pre-cooled before entering the chiller, and the chiller load and running time can be reduced.
Principle of natural cooling system for water cooling system
 
The temperature of chilled water in traditional data centers is generally 7/12 °C. For example, in Beijing, natural cooling can be used 39% of the year. If the chilled water is raised to 10/15 °C, the natural cooling time will be extended to 46%. At the same time, due to the increase of evaporation temperature, the COP of the chiller can be increased by 10%. On the other hand, as the server withstands the increase in temperature, the chilled water temperature can be further increased, and the natural cooling time throughout the year will be further extended. At present, the domestic technology-leading data center has increased the chilled water temperature to 15/21 °C, and the natural cooling time can reach 70% or even longer.
2019/05/10 20:04:16 5064 Click

主站蜘蛛池模板: 久久免费观看视频 | 成人激情视频在线 | 欧美99热 | 欧美精品a∨在线观看不卡 色网视频在线观看 | 91精品电影| 国产午夜在线观看视频播放 | 射逼网站 | 青青草国产免费国产是公开 | 秋霞电影久久久精品一区二区 | 免费一区二区 | 99riav国产精品 | 天天澡天天摸天天添视频 | 丁香色婷婷国产精品视频 | 国产尤物视频在线 | 亚洲日本无码AA在线播放 | 天天干天天操天天操 | 5060午夜电影| 精品国产视频一区二区三区 | 国产精品久久久久久久久久久久冷 | 国产精品成人无码A片免费软件 | 日韩二区三区 | 在线精品一区 | 久久久久黄 | 免费观看一级欧美在线视频 | 国产精品视频免费观看 | 欧美日韩亚洲一区二区三区 | 亚洲一区二区三 | 国产一区二区精品在线观看 | 99久久免费精品高清特色大片 | 中文字幕在线观看 | 亚洲精品一区二区三区蜜桃久 | 日日干夜夜干 | 国产精品视频一区二区三区 | 欧美aaa性bbb毛片 | 国产成人免费在线 | 欧美在线一级视频 | 久久亚洲一区二区三区四区 | 在线观看国产视频 | 欧美一级电影在线观看 | 九九综合九九 | 亚洲+变态+欧美+另类+精品 |